Awernica
AC-MER-CONT-MP1502
Canada
Supported
Avigilon

Avigilon AC-MER-CONT-MP1502

Category
Controller
First seen by Awernica
Oct 2026

Keep every device you have installed in one list – firmware, lifecycle and replacements. No card.

Latest Firmware

Not specified

No verified firmware data

Product Status

Active

Current product

Replacement

Not specified

No verified replacement

On your sites?

Add to a site

Track firmware, EOL and replacements for every device you have installed – in one list.

Specifications

From the manufacturer's product information.

MERCURY MP1502 INTELLIGENT CONTROLLER

Access Control
Supports total of 1 RS-485 IO protocol Activation/deactivation If/Then rule capabilities Anti-passback support Nested, area, hard, soft, and timed forgiveness
Door Control
Natively supports up to 4 readers and 2 opening, and can support up to 16 additional RS-485 expansion modules for a maximum of 32 entries.

GENERAL

Primary Power
12 to 24 VDC ± 10 %, 500 mA maximum (reader and USB ports not included)
Reader Port
600 mA maximum (add 600 mA to primary power current)
Micro USB Port
5 VDC, 500 mA maximum (add 270 mA to primary power current)
Battery
Memory/Clock Backup: Super Capacitor (10 days). 3 Volt Lithium, type BR2330 or CR2330 slot available for additional capacity. (CR2330 battery not included)
microSD Card
Format: microSD or microSDHC; 2GB to 8GB
Host Communication
Ethernet: 10-BaseT/100Base-TX and USB port (2.0) with optional adapter: pluggable model USB2- OTGE100
Serial I/O Device
2-wire RS-485, 2,400 to 115,200 bps, asynchronous, half-duplex, 1 start bit, 8 data bits, and 1 stop bit
Inputs
8 unsupervised/supervised, standard EOL: 1k/1k ohm, 1%, ¼ watt 2 unsupervised dedicated for cabinet tamper and UPS fault monitoring
Output Relays
4 relays, Form C; NO 5 A @ 30 VDC resistive; NC 3 A @ 30 VDC resistive

READER INTERFACE

Reader Power
12-24 VDC +/- 10% regulated, 600 mA maximum
Data Inputs
TTL compatible or 2-wire RS-485
RS-485 Mode
9,600 to 115,200 bps, asynchronous, half-duplex, 1 start bit, 8 data bits, and 1 stop bit Maximum cable length: 2000 ft. (609.6 m)
LED Output
TTL levels, high>3 V, low<0.5 V, 5 mA source/sink maximum
Buzzer Output
Open collector, 12 VDC open circuit maximum, 40 mA sink maximum

CABLE REQUIREMENTS

Power and Relays
1 twisted pair, 18 to 16 AWG
Ethernet
CAT-5, minimum
Reader TTL
6-conductor, 18 AWG, 500 ft. (152 m) maximum
Reader RS-485
1 twisted pair, shielded, 120 ohm impedance, 24 AWG, 2,000 ft. (610 m) max.
I/O Devices
RS-485 1 twisted pair with drain wire and shield, 120 ohm impedance, 24 AWG, 4,000 ft. (1,219 m) maximum
Alarm Input
1 twisted pair, 30 ohms maximum typically 22 AWG @ 1000 ft. (304.8 m) maximum

ENVIRONMENTAL

Temperature
Storage: -55° to 85° C Operating: 0° to 70° C
Humidity
5 to 95% RHNC

MECHANICAL

Dimensions
8 in. (203.2 mm) W x 6 in. (152.4 mm) L x 1 in. (25 mm) H
Weight
9 oz. (255 g) nominal, board only

COMPLIANCE AND WARRANTY

Product Compliance
UL 294 Recognized, FCC Part 15 Class A, CE Compliant, RoHS (2011/65/EU & 2015/863), EU REACH (1907/2006), California Proposition 65, NIST Certified Encryption (in process)
Third-Party Warranty
For more information, visit avigilon.com/support/warranty/third-party

Ordering information

AC-MER-CONT-MP1502
MP Series Intelligent Controller, Linux-based with 2 doors, 8 inputs and 4 outputs (Mercury part number: MP1502)